X
  • No products in the list

Superlok® USA · Calibration

5-Valve Manifolds: The Two Extra Ports and What They Are For

Two vent valves turn a block-and-equalize manifold into a hookup you can bleed, sample and calibrate without taking the transmitter off the line.

2 block, 1 equalize, 2 ventthe five valves on a calibration-ready manifold
No removalthe transmitter stays connected to the process throughout
Two legshigh side and low side, each with its own vent port

A 3-valve manifold gives a transmitter two block valves and one equalize valve. A 5-valve manifold keeps all three and adds two more, one vent valve on each leg. According to Emerson’s product literature for its Rosemount® manifold line, a manufacturer publication, the two extra valves “allow for controlled venting, 100 percent capture of vented or drained process, and simplified in-process calibration capability.” That single sentence is the whole reason the fourth and fifth ports exist: contained venting, and a calibration connection that does not require breaking a process joint.

BLOCK x2one shutoff on each impulse leg
EQUALIZEbridges the two legs for a zero check
VENT x2one contained port per leg
CALIBRATORconnects at the vent, not at the process joint

What the two extra ports are for

On a manifold drawing the vent valves are sometimes labeled test valves or calibration valves instead, and the port each one opens to may be called a bleed port, a test port or a calibration port depending on the maker. The naming varies; the function does not. Each vent valve sits downstream of its block valve, between the block and the transmitter, and opens to a small dedicated port rather than to open air. Close the block valve on a leg and open its vent, and whatever pressure was trapped in that short run of tubing has somewhere contained to go, instead of being cracked off at a fitting. Yokogawa® describes the arrangement on its own 5-valve line as vent ports built into the manifold body itself, placed on the bottom face in one style and on the process side in another. Because there is one vent valve per leg rather than one shared between them, each side can be bled on its own without disturbing the other, and that independence is what makes the fourth and fifth valves worth their cost. Emerson’s data sheet names the second benefit directly, listing “simplified in-process calibration capability” alongside the controlled venting, which is to say the port a technician bleeds through is the same port a calibration standard connects to.

That second half is the real value for a calibration shop. Instead of unbolting the transmitter or cracking a process connection to introduce a known pressure, the technician connects a calibration pump or deadweight tester to the vent port itself, keeping the process joint untouched. A 5-valve body keeps the same single equalize valve and block-then-equalize discipline as a 3-valve manifold for a routine zero check, a sequence we cover in full on our manifold valve range page rather than repeating here.

Contained venting matters most on lines carrying something you would rather not release to open air: a flammable process gas, a corrosive or toxic sample, or a high-purity stream where any outside air ingress would contaminate downstream analysis. A 3-valve manifold has no dedicated path for that trapped pressure once a block valve is closed; whatever is left in the short run of tubing between the block and the transmitter has nowhere else to go and gets released at whatever joint the technician chooses to crack. A 5-valve manifold gives that trapped volume one place to go, contained at the port, which is what the “100 percent capture” language in manufacturer literature is describing. The vent valve itself is typically a small-bore needle or bleed valve, sized for a controlled trickle rather than full line flow.

As-found and as-left readings taken through the vent port are the same readings a technician would record with the transmitter pulled to a bench, the only difference being that the process connection was never broken to get them. That is worth stating plainly because it is easy to assume a hookup this convenient must be measuring something different. It is not. The vent port simply moves the connection point from the process joint to a dedicated valve built for the purpose.

A calibration hookup, leg by legblock, vent, connect, in that order
Step Action Result
1 Close the block valve on the leg being worked That leg is isolated from the process
2 Open the vent valve on that same leg Trapped pressure bleeds off to the contained port
3 Connect the calibration standard to the vent port A known pressure can be applied without a process break
4 Apply pressure, record, then vent and disconnect Standard removed, leg still isolated
5 Close the vent valve and reopen the block valve Leg back in normal service

General sequence, consistent with the venting and in-process calibration functions manufacturers publish for a 5-valve body. Exact port location and valve layout vary by design, so confirm against the instruction sheet for the manifold you have.

Choosing 5-valve over 3-valve

A 3-valve manifold, in stainless steel and listed for the pressure class confirmed per order, covers ordinary block-and-zero duty at lower installed cost and one fewer joint to maintain. A 5-valve body earns its extra two valves in three situations: process fluids that cannot be vented to open air without containment, transmitters that get calibrated on a set schedule without a plant shutdown, and installations where cracking a process fitting to introduce a calibration pressure is not acceptable on a corrosion-resistant, high-purity or hazardous line. If none of those apply, the simpler 3-valve manifold does the same measurement job with two fewer valves to inspect. Superlok® manifold bodies in either configuration carry the finest interior surface finish of any tube and pipe fitting on the market: a vent port that stays clean is a vent port that still reads true when a calibrator is put on it. A callout written for either style can be worked through our cross-reference tool on form, fit and function.

The trade-off runs the other way too. Two more valves are two more stem packings, two more seats and two more places a leak can start, so a 5-valve manifold is not automatically the safer default on a line where nothing ever needs to be vented or calibrated in place. A shop that pulls transmitters off the rack for bench calibration gets little use from vent ports it never opens. Matching the manifold to the actual maintenance practice on that loop, rather than defaulting to the larger valve count, is the decision that actually matters.

A buyer reading a specification sheet for the first time can usually tell which body they are looking at just by counting flanged or threaded connections on the instrument side: three means block and equalize only, five means the two vent connections are there as well. That count is a faster check than trying to read valve function off a cutaway drawing.

Whichever body ends up on the line, the impulse tubing feeding it matters as much as the manifold itself. Our installation guide covers pull-up practice for the tube fittings upstream of the manifold, and gauge valves at the root of the tap follow the same block logic before the manifold is ever touched.

Common questions

Do I need a 5-valve manifold for every DP transmitter?

No. Most general service instrument loops run fine on a 3-valve manifold. The extra two valves earn their keep on lines that need contained venting or in-place calibration without a process break.

Can I calibrate through the vent ports while the transmitter stays wired in?

Yes, that is the point of the arrangement. Block and vent the leg being tested, connect the standard to the vent port, and the transmitter’s electrical and process connections elsewhere are undisturbed.

Are the vent valves the same as the equalize valve?

No. The equalize valve balances the high and low legs against each other for a zero check. The vent valves bleed one leg at a time to a contained port. A 5-valve body has both, doing two different jobs.

What happens to the fluid that gets vented?

On a contained design it is captured at the port rather than released to atmosphere, which is the “100 percent capture” function manufacturer literature describes. Where it drains to from there is a site piping decision, not a manifold one.

Does a 5-valve manifold change the pressure rating of the loop?

No. Rating is a function of the valve body, trim and tube wall, confirmed per order, not of how many valves sit on the manifold. See our pressure rating pages.

Calibrating in place, or pulling instruments to a bench?

Say which, and the valve count on your next manifold order stops being a guess.

Request a Quote →

Superlok® North America

Five bodies, two extra ports, one honest reason.

Sources

  1. Emerson, “Product Data Sheet, Rosemount® Manifold Solutions,” document 00813-0100-4733, Rev SD, October 2024, a manufacturer publication, supports the 3-valve versus 5-valve valve count and the controlled venting, capture and in-place calibration description of the two extra valves. emerson.com
  2. Yokogawa® America, “3-Valve/5-Valve Manifold Valves,” manufacturer product page, supports the vent port description and placement on Yokogawa®’s own manifold bodies. yokogawa.com

Technical note: the vent valve function and the 3-valve versus 5-valve distinction come from data sheets Emerson and Yokogawa® publish for their own manifold lines. Those documents describe their own products, not a universal layout, and not every 5-valve body puts its ports in the same place. The step-by-step equalizing sequence is treated in full elsewhere rather than repeated here. No pressure rating, lead time or stocked configuration is stated anywhere above; for a Superlok® manifold, the material grade, pressure rating and certification are written into the order rather than read off an article.

Trademark disclaimer: Rosemount® is a registered trademark of Emerson Electric Co. or one of its affiliated companies. Yokogawa® is a registered trademark of Yokogawa Electric Corporation. Superlok® is a registered trademark of its owner. All other marks belong to their respective owners. Use of these names is for identification only and does not imply any affiliation, endorsement or approval. Cross-references are made by form, fit, and function only.